Scope Precision EstimateContact Us

Fire Alarm & Low Voltage Estimating

Send your Div 28 drawings and specs. You get back an Excel and PDF estimate with device counts, raceway and cable quantities, and marked-up plan sets.

24–48 hours for most projectsTypical turnaround
Excel + marked-up PDFsOrganized by CSI section
ZIP-code pricingLocal material and labor
Price confirmed firstBefore any work starts
Sample estimate sheet
Division 28 — Electronic Safety & SecuritySample format
Line itemQtyUnitDevices
Addressable smoke detector184EA184 EA
Duct smoke detector w/ remote test22EA22 EA
Manual pull station36EA36 EA
Horn/strobe 15 cd96EA96 EA
FPLP twisted shielded pair18,400LF—
Total initiating and notification devices338 EA
Illustrative quantities. Cable shown separately by circuit.
Duct detector test stations counted

What is fire alarm and low voltage estimating?

Fire alarm and low voltage estimating is the Div 28 takeoff of initiating devices, notification appliances, modules, panels, raceway, and cable, priced in EA and LF. The deliverable is a CSI MasterFormat-organized Excel and PDF estimate with marked-up plans, using ZIP-code-adjusted material and labor pricing.

  • Devices are counted in EA; raceway and cable are measured in LF by size and rating.
  • Typical waste factors run 5–10% for cable and 3–5% for raceway, but confirm with your supplier.
  • The most common costly miss is waterflow and tamper switch interface points at the sprinkler riser.

Division 28 estimating is a device-and-circuit problem. You are not pricing a building system by volume — you are counting every initiating device, notification appliance, module, and panel, then tracing the raceway and low voltage cable that connects them. The count comes off the fire alarm floor plans and the device schedule; the pathway comes off the reflected ceiling plans, the electrical plans, and the sections. If the count is wrong, the number is wrong, and no labor factor fixes it.

Deliverable
Excel estimate + marked-up PDF plans
Organized by
CSI MasterFormat section
Turnaround
24–48 hours for most projects
Pricing
ZIP-code-adjusted material and labor pricing
Software
Bluebeam Revu, PlanSwift, RSMeans data

We take off Div 28 the way a low voltage estimator buys it: devices by type and area, raceway by size and mounting condition, cable by circuit and plenum rating, and labor by device and by pull. Where the fire alarm ties into sprinkler flow and tamper switches, elevator recall, door release, or fan shutdown, we carry those interface points as separate line items because they are separate trips and separate coordination. That tie-in work sits at the boundary with Fire Protection & Sprinkler Estimating on Div 21 and with MEP Estimating Services on Div 26 power and Div 27 communications.

Our takeoffs are organized by CSI MasterFormat section — 28 31 00, 28 31 11, 28 31 13, 28 31 16, 28 31 43, 28 31 53 — with quantities in EA for devices and LF for raceway and cable. We use Bluebeam Revu for plan markup, PlanSwift for count and linear takeoff, and RSMeans data with ZIP-code-adjusted material and labor pricing. Most projects return in 24–48 hours, and rush is available. If you also need the Div 26 feeders and branch circuits that feed the fire alarm panel, that scope belongs with MEP Estimating Services; if you are pricing a campus with access control and CCTV in the same package, those Div 28 sections are priced on the same sheet.

We also price the adjacent low voltage scope on the same sheet: structured cabling and pathway and cabling for data outlets, nurse call and intercom stations, and AV system rough-in, each counted by device and by pull. For a fire alarm estimate for contractors, the deliverable is a material takeoff organized by section, with horn strobe and speaker strobe counts split by circuit, battery backup calculation inputs, and a point-to-point wiring schedule. We flag ADA compliance locations and note where a submittal or RFI is needed before the bid package is final. If your package also includes access control and CCTV, those Div 28 sections are priced on the same sheet.

Services

What our fire alarm takeoff covers

We price the fire alarm and low voltage scope from the device schedule, the floor plans, and the riser diagram, and we separate the work that is ours from the work that belongs to the electrical sub or the sprinkler contractor. Every quantity is tied to a drawing sheet or a specification section so you can check it.

Initiating Devices

Addressable smoke, heat, and duct detectors counted by area, mounting type, and ceiling condition.

EA

Notification Appliances

Horn/strobe and speaker/strobe appliances priced by candela rating, dB level, and mounting height.

EA

Panels & Annunciators

Fire alarm control panels, remote annunciators, and NAC boosters priced with battery backup sizing.

EA · LS

Raceway

EMT, RGS, MC, and PVC raceway measured by size, mounting condition, and support spacing.

LF

Cable

FPLP, FPLR, and FPL cable measured by circuit and plenum rating, including home runs to panels.

LF

Interface Modules

Monitor and control modules for fan shutdown, door release, elevator recall, and sprinkler flow/tamper switches.

EA

Boxes & Cabinets

Junction boxes, pull boxes, and terminal cabinets counted by size and wall type for rough-in.

EA

Testing & Documentation

Programming, testing, and acceptance test documentation priced as a lump sum by system size.

LS

What every fire alarm & low voltage estimating takeoff includes

  • Addressable smoke, heat, and duct detectors — EA by area and mounting type
  • Manual pull stations — EA at egress doors and exit paths
  • Horn/strobe and speaker/strobe appliances — EA by candela and dB rating
  • Fire alarm control panel, remote annunciator, and NAC boosters — EA
  • Addressable monitor and control modules — EA for fan shutdown and door release
  • Waterflow and tamper switch connections at riser and zone valves — EA
  • Raceway — LF of EMT, RGS, MC, and PVC by size and mounting condition
  • Fire alarm cable — LF of FPLP, FPLR, and FPL by circuit and plenum rating
  • Junction boxes, pull boxes, and terminal cabinets — EA by size
  • Device rough-in counts by wall type — CMU, gypsum, metal stud
  • Programming, testing, and acceptance test documentation — LS by system size
  • Battery backup sizing for 24-hour standby plus 5-minute alarm — LS
How we work

How we do a low voltage takeoff on Div 28

  1. Device schedule and floor plan countWe start with the fire alarm device schedule and the floor plans. Every smoke detector, heat detector, pull station, horn/strobe, and module is counted by type and by area — corridor, suite, common, storage, mechanical. We mark each device on the plan set with a symbol and a tag number so the count is auditable. If the schedule and the plans disagree, we flag it and ask which governs.
  2. Raceway routing and measurementWe trace each raceway run from the device to the nearest junction box and back to the FACP or booster. Runs are measured by size — 1/2 in, 3/4 in, 1 in — and by mounting condition: exposed, concealed in wall, above ceiling, or underground. We note where the spec requires EMT versus RGS versus MC, and where plenum-rated cable is required above ceilings used as return air plenums.
  3. Cable pulls by circuitCable is measured by circuit, not by device. We trace the signaling line circuit (SLC) and each notification appliance circuit (NAC) from the panel to the last device, add 10% slack at each pull point, and separate FPLP plenum from FPLR riser and FPL non-plenum. Twisted shielded pair for SLC is counted separately from unshielded notification circuit cable.
  4. Interface and tie-in pointsWe list every point where the fire alarm system touches another trade: sprinkler flow and tamper switches, elevator recall and shunt trip, magnetic door holders, fan shutdown, and the fire pump controller feed. Each interface is a separate line item with its own module, raceway, and labor, because each one is a separate trip and a separate coordination item with the sprinkler and elevator contractors.
  5. NAC load and voltage drop checkBefore we price the notification circuits, we check the NAC load. We total the candela ratings and current draw on each circuit, compare against the booster or panel output, and run a voltage drop calculation at the end of the run. If the drop exceeds the appliance rating, the circuit needs larger wire or an additional booster — and that changes the material and labor number.
  6. Labor, pricing, and assemblyDevices are priced by type with labor hours per device, adjusted for mounting condition — a detector in a hard-lid corridor takes longer than one in an accessible ceiling. Raceway and cable are priced by LF with labor by size and pull condition. Material is ZIP-code-adjusted. The final estimate is assembled in Excel by CSI section with a PDF markup set showing every counted device and measured run.

What we need from you

  • Fire alarm plansFloor plans showing device locations, the riser diagram, and the device schedule. If the schedule is on a separate sheet, send that too.
  • Electrical plansFor the Div 26 power feed to the FACP, booster, and any remote annunciator, plus the circuit breakers and disconnects.
  • Mechanical plansDuct detector locations, sampling tube sizes, and remote test station locations. These are often shown only on the mechanical sheets.
  • Specification bookDiv 28 sections 28 31 00 through 28 31 53, plus any Div 26 and Div 27 sections that specify the cable and raceway.
  • Manufacturer and platformNotifier, Simplex, Edwards, Honeywell, or Potter. Device and programming costs differ by platform, and the spec usually names one.
  • Ceiling and wall typesReflected ceiling plans and wall sections. Plenum ceilings, hard lids, and CMU walls change the raceway and cable method.
  • Bid date and scope splitWhen the bid is due, and whether you are pricing the fire alarm as a prime or as a sub to the electrical contractor.
Sample output

Sample fire alarm takeoff format

This is how a Div 28 takeoff is organized in the Excel deliverable. Each line carries a CSI section, a quantity, a unit, and a drawing reference.

Sample format — illustrative quantities
SectionLine itemQtyUnitRef.
28 31 13Addressable smoke detector, area type corridor184EAFA-101
28 31 43Duct smoke detector with sampling tube and remote test station22EAM-201
28 31 16Horn/strobe, 15 cd, wall mounted96EAFA-102
28 31 11Fire alarm control panel with battery and enclosure1EAFA-001
28 31 11NAC booster power supply, 6 amp4EAFA-001
28 31 53Waterflow switch connection at riser6EAFP-101
26 05 33EMT raceway, 3/4 in, concealed above ceiling4,200LFE-201
28 31 13FPLP twisted shielded pair, SLC circuit18,400LFFA-001
28 31 16FPLR notification circuit cable, 14 AWG6,800LFFA-102
28 31 19Remote annunciator with terminal cabinet2EAFA-001

Units of measure in fire alarm cost estimating

Div 28 quantities are counted in EA for devices and measured in LF for raceway and cable. The unit you buy in is not always the unit you count in, so we show both.

ItemUnitHow it's measured
Initiating devicesEACounted each from the device schedule and floor plans by area type
Notification appliancesEACounted each by candela rating, dB rating, and wall or ceiling mounting
Fire alarm control panelEACounted each with enclosure, battery, and terminal cabinet
Conduit and racewayLFMeasured along the run by size, from device to panel, including risers
Fire alarm cableLFMeasured by circuit from panel to last device, plus 10% slack
Plenum-rated cableLFMeasured separately for runs above ceilings used as return air plenums
Terminal cabinets and boxesEACounted each by size and location from the riser and floor plans
Labor by device typeHREstimated hours per device by type and mounting condition
Programming and testingLSLump sum by system size and number of addressable points

Worked example: fire alarm estimate for a small commercial floor

This example takes off a single 12,000 sq ft office floor with a 100-point addressable fire alarm system. All dimensions and quantities are illustrative. We show every calculation so you can follow the method and apply it to your own project.

Step 1 — Count devices from the floor plan and schedule

  • Walk the plan and tally each device by type and area. Assume: 24 smoke detectors (corridor and suite), 2 duct detectors (mechanical), 4 heat detectors (storage), 6 pull stations, 18 horn/strobes, 1 FACP, 1 remote annunciator, 8 monitor modules, 4 control modules.
  • Total initiating devices: 24 smoke + 2 duct + 4 heat + 6 pull = 36 EA.
  • Total notification appliances: 18 EA.
  • Total panels and annunciators: 2 EA.
  • Total modules: 12 EA.

Step 2 — Measure raceway runs

  • For each device, trace the raceway to the nearest junction box and then to the panel.
  • Assume average run per device: 30 LF for smoke detectors, 50 LF for duct detectors (mechanical room), 25 LF for heat detectors, 40 LF for pull stations, 35 LF for horn/strobes.
  • Raceway total: (24×30) + (2×50) + (4×25) + (6×40) + (18×35) = 720 + 100 + 100 + 240 + 630 = 1,790 LF.
  • Add 10% for slack and vertical drops: 1,790 × 1.10 = 1,969 LF. Round to 1,970 LF.
  • Separate by size: assume 80% 3/4 in EMT (1,576 LF) and 20% 1 in EMT (394 LF).

Step 3 — Calculate cable by circuit

  • SLC cable: one twisted shielded pair per circuit. Assume 2 SLC circuits. Average length per circuit: 1,200 LF. Total SLC: 2 × 1,200 = 2,400 LF. Add 10% slack = 2,640 LF.
  • NAC cable: 4 circuits. Average length per circuit: 800 LF. Total NAC: 4 × 800 = 3,200 LF. Add 10% = 3,520 LF.
  • Plenum rating: assume 60% of cable runs above a return air plenum. FPLP cable: (2,640 + 3,520) × 0.60 = 3,696 LF. FPLR cable: remainder = 2,464 LF.

Step 4 — Count boxes and terminations

  • Junction boxes: one per device plus one per pull point. Assume 1.2 boxes per device: (36+18+12) × 1.2 = 79 EA. Round to 80 EA.
  • Terminal cabinets: 2 EA (one at FACP, one at remote annunciator).
  • End-of-line resistors: one per NAC circuit = 4 EA.

Step 5 — Apply waste and labor

  • Waste factor: typical 5% for devices, 10% for cable, 5% for raceway.
  • Device waste: 36 initiating × 1.05 = 38 EA; 18 notification × 1.05 = 19 EA; 12 modules × 1.05 = 13 EA.
  • Cable waste: SLC 2,640 × 1.10 = 2,904 LF; NAC 3,520 × 1.10 = 3,872 LF.
  • Raceway waste: 1,970 × 1.05 = 2,069 LF.
  • Labor: use typical hours per device (e.g., 1.5 HR per smoke detector, 2.0 HR per duct detector, 1.0 HR per pull station, 1.2 HR per horn/strobe). Total labor = (24×1.5) + (2×2.0) + (4×1.5) + (6×1.0) + (18×1.2) + (12×0.8) + (2×4.0) = 36 + 4 + 6 + 6 + 21.6 + 9.6 + 8 = 91.2 HR. Add 15% for programming and testing = 104.9 HR.

This method gives you a complete material and labor takeoff. Adjust the assumptions to match your project's drawings and specifications.

Cost drivers

What moves the low voltage cost estimating number

Relative impact on a typical estimate for this trade, based on estimator judgment. Select a bar for details.

Scale: 1 = minor, 5 = major relative impact. Estimator judgment, not measured data.
Relative impact 5 / 5

Device count

The single largest driver. A mid-size commercial floor might carry 40 to 60 initiating devices and 30 to 50 notification appliances. Every added device adds material, labor, box, and cable drop. If the device schedule is missing or incomplete, the count is an assumption, not a takeoff.

Device count

The single largest driver. A mid-size commercial floor might carry 40 to 60 initiating devices and 30 to 50 notification appliances. Every added device adds material, labor, box, and cable drop. If the device schedule is missing or incomplete, the count is an assumption, not a takeoff.

System type

Conventional panels use zone wiring and fewer modules but more home-run cable. Addressable panels use less cable but every device has an address and the programming labor is higher. Hybrid systems split the difference. The spec usually names the platform, and the platform changes both the device cost and the programming hours.

Cable rating

FPLP plenum cable costs more per LF than FPLR riser or FPL non-plenum. If the ceiling is used as a return air plenum, the spec requires plenum-rated cable for the entire run above that ceiling. This is a material swing that shows up as a line item, not a rounding error.

Raceway method

EMT is the baseline. RGS costs more in material and labor and is often required in mechanical rooms, parking garages, and exterior runs. MC cable is faster to install but not always accepted by the AHJ. Underground PVC requires trenching, bedding, and pull boxes. The method is set by the spec and the mounting condition.

Interface count

Every sprinkler flow switch, tamper switch, elevator recall point, door holder, and fan shutdown is a separate module, a separate raceway run, and a separate coordination item. A building with 6 risers and 20 door holders carries 26 interface points that do not appear in the device count on the floor plan.

Testing and acceptance

Programming, point-to-point testing, and the fire marshal acceptance test are labor, not material. A 300-point addressable system takes longer to program and test than a 100-point system, and the documentation — as-builts, O&M manuals, and owner training — is a lump sum that scales with system size.

Plenum ceiling area

The square footage of ceiling used as a return air plenum drives the quantity of FPLP cable and the labor to pull it. Mechanical drawings show which ceilings are plenums. A building with 40,000 sq ft of plenum ceiling may require 12,000 LF of plenum-rated cable that would otherwise be FPLR. This is a material and labor swing that must be measured, not estimated.

Mounting height and access

Devices mounted above 10 ft require a lift or scaffold. Hard-lid ceilings and occupied spaces slow the work. A horn/strobe at 12 ft in a warehouse takes longer to install than one at 8 ft in an office corridor. We adjust labor hours per device by mounting height and access condition.

Scope gaps

Common scope gaps in fire alarm bid estimating

Most Div 28 misses are not math errors. They are items that live on another trade's sheet or in a spec section nobody read. We check for these on every takeoff.

  • Duct detector access panels and remote test stations are shown on the mechanical plans, not the fire alarm sheets. If you count only the FA sheets, you miss the panel, the test station, and the raceway to reach it. We cross-check the mechanical drawings against the device schedule.
  • Sprinkler flow and tamper switch connections sit at the boundary between Div 21 and Div 28. The sprinkler contractor furnishes the switch; the fire alarm contractor wires it. The module, the raceway, and the labor are often left out of both bids. We carry them as separate line items.
  • Elevator recall and shunt trip interface to the elevator controller requires a module at the machine room, a detector in the pit and the hoistway, and a raceway run to the controller. This is frequently shown only on the elevator shop drawings, which are not available at bid time. We flag it as an allowance.
  • Magnetic door holders and door release hardware on corridor and stair doors are sometimes specified under Div 08 hardware and sometimes under Div 28. If the hardware spec section lists them, the fire alarm estimate should not double-count them — but the wiring and module still belong in Div 28.
  • NAC circuit voltage drop is a calculation, not a count. A circuit with 12 strobes at 15 cd on 14 AWG may drop below the appliance rating at the end of the run. The fix is larger wire or a booster, and both change the number. We run the calculation before pricing the circuit.
  • Plenum-rated cable is required above ceilings used as return air plenums, and the mechanical drawings show which ceilings those are. If the fire alarm spec says FPLP but the ceiling is not a plenum, you are over-pricing; if the spec says FPLR and the ceiling is a plenum, you are under-pricing and the AHJ will reject it.
  • Fire-rated wall and floor penetrations require listed firestop assemblies, and the fire alarm raceway crosses those walls. The firestop is usually a separate Div 07 section, but the labor to seal around the raceway is real. We note the penetrations and flag the firestop to the GC.
  • Battery backup sizing for 24-hour standby plus 5-minute alarm is a calculation based on the total standby load of the panel and all connected devices. If the panel is specified with a standard battery and the load exceeds it, the battery and enclosure change. We check the load against the specified battery.
  • As-built drawings, O&M manuals, and owner training hours are specified in Div 28 but rarely priced. They are a lump sum that scales with system size and the number of addressable points. We carry them as a separate line so you can see the cost.
  • Permit, plan review, and fire marshal inspection fees are jurisdiction-specific. The adopted code edition and the fee schedule vary by city and county. We exclude them from the takeoff and tell you to confirm the fees with the local building department.

Materials axis: system types and low voltage cable

The choice of system architecture and cable rating drives material cost and labor. This table compares common options.

System typeCable typeRacewayTypical use
ConventionalFPLR or FPLPEMTSmall buildings, low device count
AddressableFPLP twisted shielded pairEMT or MCLarge buildings, many devices
HybridFPLP or FPLREMTMixed systems with zones and addresses
Voice evacuationFPLP twisted shielded pairEMTAssembly occupancies, high-rise
WirelessNone (mesh)NoneRetrofit, historic buildings
Codes and standards

Codes and standards behind a fire alarm estimate for contractors

Model codes

NFPA 72 (National Fire Alarm and Signaling Code) is the primary installation standard and sets device spacing, circuit performance, and testing requirements. NFPA 70 (NEC) governs wiring methods, including Article 760 for fire alarm systems. The International Building Code (IBC) and International Fire Code (IFC) adopt these by reference and add requirements for occupancy-specific systems. The edition adopted varies by jurisdiction; confirm with the local building department. NEC Article 760.24 requires plenum-rated cable in environmental air spaces, which directly affects material cost.

Industry standards

NECA/IESNA 500 and 502 provide recommended installation practices for fire alarm systems and should be referenced for labor units. UL 864 covers control units, and UL 268 covers smoke detectors. Factory Mutual (FM) and Underwriters Laboratories (UL) listings are often required by spec. These standards influence device selection and testing documentation, which adds labor.

Specification sections

You must read CSI MasterFormat Division 28 sections: 28 31 00 Fire Detection and Alarm, 28 31 11 Control Panels, 28 31 13 Addressable Initiating Devices, 28 31 16 Notification Appliances, 28 31 19 Remote Annunciators, 28 31 33 Smoke Detectors, 28 31 43 Duct Smoke Detectors, and 28 31 53 Waterflow and Tamper Switches. Also check Division 26 for power and Division 27 for communications. These sections specify device types, cable ratings, and testing requirements, all of which change quantities and cost.

Local amendments

Local jurisdictions often amend model codes, changing device spacing, requiring additional notification appliances, or mandating specific system types. For example, some cities require voice evacuation in all high-rises, while others allow horn/strobes. Adopted editions of NFPA 72 and NEC vary by state and city. Always confirm the adopted code edition and local amendments with the local building department before finalizing your estimate. This step prevents costly surprises during permitting and inspection.

Who we provide estimates for

Who uses this fire alarm estimator output

Electrical contractors

You are bidding the fire alarm as part of a Div 26 package and need a defensible number for the Div 28 scope. You use the device count and cable quantities to check your own takeoff, and the interface line items to see what the fire alarm sub will ask you to carry.

Low voltage subcontractors

You bid fire alarm, access control, and CCTV and need a fast, accurate takeoff to decide which projects to pursue. You use the estimate to set your number, and the marked-up plan set to hand to your foreman for installation.

General contractors

You are comparing fire alarm sub bids and need a third-party number to check the low bid. You use the Div 28 takeoff to see whether the sub counted the duct detectors, the interfaces, and the plenum cable, or whether the bid is missing scope.

Developers and owners

You are budgeting a project before the design is complete and need a realistic Div 28 number. You use the estimate to set the budget and to understand which decisions — system type, cable rating, interface count — move the cost the most.

Architects and engineers

You are checking a contractor's bid against your design intent and need to see whether the device count matches the drawings. You use the takeoff to confirm that the specified system and the priced system are the same.

Where we provide estimates

Fire Alarm & Low Voltage Estimating in 20 states

Pricing is adjusted to the project ZIP code. Select a highlighted state to see the cities we cover there.

States we coverSelected
TX

Fire Alarm & Low Voltage Estimating in Texas

Nation's largest construction market; Sun Belt population growth, data centers, semiconductor plants, and single-family home building.

Texas estimating services
Property types

Project types and what changes in the takeoff

The Div 28 takeoff method stays the same, but the device mix, raceway conditions, and interface count shift by building type. Below are common project types and what to watch for.

Office building

More notification appliances in corridors, fewer duct detectors; plenum ceilings common.

Watch for: Verify ceiling plenum and device spacing per NFPA 72.

Warehouse / industrial

High ceilings require longer raceway runs and lifts; heat detectors instead of smoke in storage.

Watch for: Check mounting height and access for labor adjustment.

Healthcare facility

Many duct detectors, door holders, and interface points; stricter code requirements.

Watch for: Coordinate with mechanical and elevator trades for interfaces.

K-12 school

Numerous pull stations and horn/strobes; often requires voice evacuation system.

Watch for: Confirm speaker/strobe vs horn/strobe and circuit load.

Multi-family residential

Smoke detectors in each unit, sounder bases; often conventional panels.

Watch for: Count devices per unit and common areas; verify wiring method.

Data center

Very early warning smoke detection (VESDA) and clean agent interface.

Watch for: Specialty devices and modules increase cost; check spec.

Retail shell

Core and shell system with tenant fit-out allowances.

Watch for: Clarify scope split between landlord and tenant.

Parking garage

Heat detectors, pull stations, and notification appliances in open structures.

Watch for: Raceway often exposed; use EMT or RGS as specified.

Deliverables

What you receive

  • An Excel workbook organized by CSI MasterFormat Div 28 section, with quantities in EA and LF, unit costs, and extended totals.
  • A PDF estimate with the same line items, formatted for review and markup.
  • A marked-up plan set in Bluebeam Revu showing every counted device with a symbol and tag, and every measured raceway and cable run.
  • A device schedule cross-check noting any disagreement between the schedule and the floor plans.
  • A NAC load and voltage drop summary for each notification circuit, with any required booster or wire size change flagged.
  • An interface list covering sprinkler flow and tamper switches, elevator recall, door holders, and fan shutdown, with quantities and drawing references.
  • A list of exclusions and assumptions, including permit fees and firestop, with a note to confirm the adopted code edition with the local building department.
Checklist

Pre-bid checklist for fire alarm and low voltage takeoff

  • Confirm adopted code edition with local building department.
  • Verify device schedule matches floor plans; note discrepancies.
  • Check mechanical plans for duct detector locations and test stations.
  • Review spec for plenum-rated cable requirements above ceilings.
  • Count all interface points: sprinkler flow/tamper, elevator recall, door holders.
  • Run NAC voltage drop calculations for each circuit.
  • Confirm battery backup sizing for 24-hour standby plus 5-minute alarm.
  • Identify fire-rated wall penetrations and firestop requirements.
  • Check for seismic bracing requirements in raceway.
  • Clarify scope split between fire alarm sub and electrical sub.
  • Include programming, testing, and as-built documentation in labor.
  • Exclude permit and inspection fees; confirm with GC.
Client reviews

What clients say about Scope Precision Estimate

10 client reviews
RW
Robert WilliamsEstimating Manager

Professional and reliable estimating service. The detailed quantity takeoff helped us reduce pricing errors and submit our proposal on time.

JR
James RichardsonConstruction Project Manager

Excellent construction estimating service. The team provided a comprehensive takeoff and cost breakdown that saved us hours of manual work.

KM
Kevin MartinezCivil Contractor

Great experience from start to finish. The detailed material takeoff and cost estimate helped us prepare a much more accurate project budget.

DT
Daniel ThompsonCommercial Contractor

Very impressed with the accuracy and turnaround time. Their estimate gave us a clear picture of material and labor costs before starting the project.

SH
Steven HarrisCommercial Builder

The quality of the estimate exceeded our expectations. Their detailed breakdown of labor, materials, and project costs gave us confidence in our bid.

MA
Michael AndersonGeneral Contractor

The cost estimate was detailed, accurate, and easy to understand. It helped us prepare our bid confidently and stay competitive without overlooking important costs.

FAQ

Fire Alarm & Low Voltage Estimating questions

What is the typical turnaround time for a fire alarm estimate?

Most projects return in 24–48 hours. Rush service is available for an additional fee. Turnaround depends on the completeness of the drawings and specifications. If the device schedule is missing or the plans are not coordinated, we may need to request additional information, which can extend the timeline. We will notify you if we need anything to complete the takeoff. For example, if duct detector locations are not shown on mechanical plans, we must ask for them before finalizing quantities.

Do you use RSMeans for pricing?

Yes, we use RSMeans data for material and labor pricing, adjusted by ZIP code for your project location. RSMeans provides a baseline, but we also incorporate current market pricing for fire alarm devices and cable when it differs significantly. The final estimate reflects both the published data and our recent project experience. For instance, if copper prices have risen since the last RSMeans update, we adjust cable costs accordingly. We also factor in local labor rates and productivity factors.

How do you handle proprietary specifications that name a specific manufacturer?

We take off the system as specified. If the spec names Notifier, Simplex, Edwards, Honeywell, or Potter, we use that manufacturer's device and programming costs. If you want an alternate price, we can provide a separate estimate with a different platform. Note that proprietary specs may limit competition and affect pricing. For example, a Notifier NFS2-3030 panel may cost more than a comparable addressable panel from a non-proprietary line, and programming software may be restricted to authorized dealers.

What if the fire alarm plans are not complete or are in design?

We can work with incomplete plans by making reasonable assumptions based on typical layouts and code requirements. We will clearly state those assumptions in the estimate. However, the accuracy of the takeoff depends on the level of detail provided. For design-build or early budgeting, we can provide a conceptual estimate with a range of accuracy. For example, if the floor plan lacks device locations, we may assume one smoke detector per 900 sq ft and note that assumption in the basis of estimate.

Do you include the electrical power feed to the fire alarm panel?

The power feed from the electrical panel to the fire alarm control panel is typically part of Division 26 and is not included in our Div 28 takeoff. We can include it if you provide the electrical plans and request it. Otherwise, we will note it as an exclusion so you can account for it separately. This includes the dedicated 120 VAC circuit, disconnect means, and any surge protection. We recommend confirming with the electrical contractor to avoid double-counting.

How do you calculate labor hours for fire alarm devices?

We use industry-standard labor units, adjusted for device type, mounting height, and access conditions. For example, a smoke detector in an accessible ceiling might take 1.5 hours, while one in a hard-lid ceiling might take 2.5 hours. We also add labor for programming, testing, and documentation based on the number of addressable points. For instance, a system with 100 addressable points might require 16 hours of programming and 8 hours of testing, plus additional time for as-built drawings.

What is a NAC voltage drop calculation and why does it matter?

NAC stands for Notification Appliance Circuit. Voltage drop is the loss of voltage along the wire due to resistance. If the drop is too high, the appliances at the end of the circuit may not operate properly. We calculate the drop for each circuit to ensure the wire size and booster capacity are adequate. If not, we flag the need for larger wire or additional boosters, which affects cost. For example, a 2 A circuit with 200 ft of 14 AWG wire may have a drop that exceeds the 10% limit, requiring 12 AWG or a booster.

Do you provide a marked-up plan set with the estimate?

Yes, we provide a marked-up plan set in Bluebeam Revu showing every counted device with a symbol and tag, and every measured raceway and cable run. This allows you to verify our takeoff and use the marked set for installation planning. The markup is included in the PDF deliverable. For example, each smoke detector is marked with a circle and a unique tag (e.g., SD-101), and each raceway run is highlighted with its length and size noted in the comments.

How do you handle fire alarm interfaces with other trades?

We list every interface point as a separate line item, including sprinkler flow and tamper switches, elevator recall, door holders, and fan shutdown. Each interface includes the module, raceway, and labor required. We coordinate with the specifications to ensure these items are not double-counted with other divisions, such as Div 21 or Div 08. For example, a sprinkler flow switch may be provided under Div 21, but the monitor module and wiring are Div 28; we note the split clearly.

Can you estimate access control and CCTV as part of the low voltage package?

Yes, we can estimate Division 28 sections for access control (28 10 00) and CCTV (28 20 00) if they are part of your scope. These systems have different device counts and cabling requirements. We will take them off separately and organize them by CSI section. Note that they may require coordination with Div 27 communications. For example, access control readers may need Cat6 cable and power supplies, while CCTV cameras may require PoE switches and licensing.

What is your pricing basis and how do you adjust for location?

We use ZIP-code-adjusted material and labor pricing based on RSMeans data. This accounts for regional variations in material costs and labor rates. If you have specific pricing for devices from a supplier, we can incorporate that. The goal is to provide a realistic number that reflects your project's location. For instance, labor rates in New York City are significantly higher than in rural Texas, and material freight costs can vary. We adjust both material and labor components using the latest RSMeans city cost indexes.

How do you handle firestopping and seismic bracing in the estimate?

Firestopping of fire-rated penetrations is typically specified under Division 07 and is excluded from our Div 28 takeoff. However, we note the penetrations and flag the firestop to the GC. Seismic bracing of raceway is required in some jurisdictions and is excluded unless specifically requested. We can include it if you provide the requirements. For example, in California, seismic bracing may be required for raceway over 2.5 in. We will add labor and material for seismic fittings and supports if requested.

What does an outsourced fire alarm estimating company need from me to start a takeoff?

Send the fire alarm floor plans, device schedule, and specifications. We also need the reflected ceiling plans for pathway and cabling, the electrical plans for panel feeds, and any addenda or RFI responses. If you have a point-to-point wiring schedule or a battery backup calculation from the engineer, include it. We work in Bluebeam Revu and PlanSwift, and return Excel and PDF marked-up plan sets in 24–48 hours for most projects.

Can you provide low voltage estimating services for structured cabling and AV system scope?

Yes. We count data outlets, patch panels, and cable pulls for structured cabling, plus AV system rough-in, intercom, and nurse call stations. Each is carried by device and by pull, with plenum-rated low voltage cable separated from riser. Pathway and cabling is measured in LF from the reflected ceiling plans and sections. If the package includes Div 28 fire alarm, we price both on the same sheet so the bid package totals stay aligned.

How do you handle prevailing wage and ADA compliance in a fire alarm bid estimate?

Prevailing wage projects require certified payroll rates, so we price labor at the applicable wage determination rather than open-shop rates, and we note the wage source in the estimate. For ADA compliance, we check mounting heights for horn strobe and speaker strobe devices and reach ranges for pull stations against the drawings. Any conflict between the device schedule and the ADA details becomes an RFI item before the bid package is submitted.

RH

Reviewed by Ryan H.

Senior Estimator, 15+ years in construction estimating and cost planning. is a Senior Estimator with more than 15 years of professional experience in construction estimating and cost planning.

  • Construction cost estimating
  • Quantity takeoffs
  • Material and labor cost analysis
  • Bid preparation and evaluation
  • Drawing and specification review
  • Project budgeting

Get your Div 28 estimate

Send your fire alarm and low voltage drawings and specs for a detailed takeoff in 24–48 hours.

  1. We review the set and check for missing sheets or addenda.
  2. You get a quote with a price and a delivery date.
  3. You approve and we start the takeoff.
  4. You receive the Excel estimate and marked-up plans.
Upload plans for a quote
Call Us